TAPMOTION® ED ISM®
YOUR BENEFITS AT
A GLANCE
|
Product description
ISM® is a cost-effective monitoring system. It is not just beneficial for use on new transformers but also on older transformers, making them ready for future requirements. Our aim is to realise your wishes for the system solutions. Our services do not only include supplying a piece of equipment: We want to understand your questions and problems, to advise you professionally and, where necessary, work with you to develop optimal solutions tailored to your needs.
There is an integrated web server which makes any annoying installation of software on your computer unnecessary. In addition, we offer you a large choice of control system protocols.
From now on, you can order the tried and tested motor drive unit TAPMOTION® ED with additional intelligence – the ISM® module – ex works. Depending on the situation on site, this ISM® module can, however, be built-in to a separate control cabinet or even, depending on the space available, in an existing motor drive unit cabinet. Our full range also includes the building and engineering of control cabinets.
Our service includes:
- Survey
- Consultation
- Establishing a solution together
- Engineering
- Development and implementation
- Commissioning
- Support
Technical data
Function |
Scope |
Input/Output |
Monitoring of the motor drive unit |
Tapping position |
Digital |
Motor signals |
Digital, analogue |
|
Monitoring OLTC |
Contact wear |
|
Maintenance interval |
|
|
Tap-changer maintenance book |
|
|
Operational statistics |
|
|
Oil filter overpressure |
Digital |
|
Motor current, single-phase |
Analogue |
|
Protective relay RS2001 |
Digital |
|
Transformer monitoring |
Ambient, oil (top), hotspot and open temperature sensors |
Analogue |
Load current and voltage |
Analogue |
|
Load factor |
|
|
Performance (S, P, Q) |
|
|
Ageing rate |
|
|
Buchholz relay |
Digital |
|
Overpressure discharge (pressure safety valve) triggered |
Digital |
|
Oil level (min, max) |
Digital |
|
Oil quality |
|
|
Maintenance interval |
|
|
Data logging |
Continual recording of all values measured and calculated |
|
Event log |
|
|
Communication with control centres |
IEC61850 |
RJ45, LWL |
IEC60870-5-101 |
RS232, RS485, LWL |
|
IEC60870-5-104 |
RJ45, LWL |
|
ModBus TCP |
RJ45, LWL |
|
Viewing and operation |
Viewing via web server including status information |
|